Water distribution formulas & conversions
ABC/WPI distribution exams and many state-written exams hand you a formula/conversion sheet. Knowing the formulas isn't the hard part — choosing the right one and keeping the units straight is. Here is every formula you'll use, when to use it and a worked example.
Conversions to know cold
| 1 ft³ of water | 7.48 gallons | Turns a volume in cubic feet into gallons. |
| 1 gallon of water | 8.34 pounds | The heart of the pounds formula. |
| 1 psi | 2.31 ft of water (head) | Pressure → height of water. |
| 1 ft of water | 0.433 psi | Height of water → pressure (1 ÷ 2.31). |
| 1 MGD | 694 gpm ≈ 1.55 ft³/s | Million gallons per day to minute and second rates. |
| 1 ft³/s (cfs) | 448.8 gpm | Used when velocity × area gives cfs. |
| 1 day | 1,440 minutes | Daily flow ↔ per-minute flow. |
| 1 % | 10,000 mg/L | Product strength → concentration. |
| 1 hp | 0.746 kW | Horsepower ↔ kilowatts. |
| 1 yd³ | 27 ft³ | Trench excavation and backfill. |
Area of a circle (pipe or tank)
Area (ft²) = 0.785 × D² (D in feet)
Any round pipe or tank. 0.785 is π ÷ 4, so you can use the diameter directly.
Example. Cross-sectional area of an 8-inch main?
- 8 in ÷ 12 = 0.667 ft
- 0.785 × 0.667² = 0.349 ft²
Common trap: Forgetting to convert inches to feet before squaring.
Volume of a pipe or cylindrical tank
Volume (gal) = 0.785 × D² × L × 7.48
Gallons to fill, flush or disinfect a main; tank capacity.
Example. Gallons in 1,000 ft of 12-inch main?
- 0.785 × 1² = 0.785 ft²
- 0.785 × 1,000 ft = 785 ft³
- 785 × 7.48 = 5,872 gal
Flow, velocity and area
Q (ft³/s) = A (ft²) × V (ft/s)
Velocity in a main, the flow needed to reach a flushing velocity, or flow from velocity.
Example. Velocity of 500 gpm in a 6-inch main?
- 500 gpm ÷ 448.8 = 1.114 ft³/s
- A = 0.785 × 0.5² = 0.196 ft²
- V = 1.114 ÷ 0.196 = 5.68 ft/s
Common trap: Mixing gpm with ft³/s — convert first.
Pressure and head
Head (ft) = psi × 2.31 · psi = ft × 0.433
Static pressure from tank elevation, gauge readings at different elevations.
Example. Static pressure at a hydrant 120 ft below the tank water surface?
- 120 ft × 0.433 = 52.0 psi
Common trap: Using pipe length instead of vertical height.
Chlorine dose, demand and residual
Dose = Demand + Residual (mg/L)
Any time two of the three are known.
Example. Dose 2.5 mg/L, residual 0.6 mg/L — demand?
- Demand = 2.5 − 0.6 = 1.9 mg/L
Pounds formula
lb/day = Flow (MGD) × Dose (mg/L) × 8.34
Chemical feed rates, or pounds of chlorine for a volume (use MG instead of MGD).
Example. Pounds of chlorine to dose 0.15 MG of new main at 25 mg/L?
- 0.15 × 25 × 8.34 = 31.3 lb of available chlorine
Common trap: Dividing by the product strength: 65% calcium hypochlorite needs 31.3 ÷ 0.65 = 48.1 lb of product.
Detention time / water age
Detention time = Volume ÷ Flow (same units)
How long water stays in a tank or main.
Example. A 500,000-gal tank with 350 gpm outflow and no inflow: hours to drain?
- 500,000 ÷ 350 = 1,429 min
- 1,429 ÷ 60 = 23.8 h
Water horsepower
whp = gpm × Total head (ft) ÷ 3,960
Pump power; then brake hp = whp ÷ pump efficiency and motor hp = bhp ÷ motor efficiency.
Example. 800 gpm against 150 ft, pump 78%, motor 92% — motor hp?
- whp = 800 × 150 ÷ 3,960 = 30.3
- bhp = 30.3 ÷ 0.78 = 38.8
- mhp = 38.8 ÷ 0.92 = 42.2 hp
Common trap: Multiplying by efficiency instead of dividing — the motor always needs more power than the water receives.
Practice the math
Fifteen free problems with step-by-step solutions — then the full course drills every formula with interactive illustrations.