Hydrant Flow Test: Procedure, Formula and Worked Examples

A hydrant flow test measures how much water a main can deliver: you read static pressure at a test hydrant, open a nearby flow hydrant fully, then read the pitot pressure at the flowing outlet and the residual pressure at the test hydrant. Flow is Q = 29.83 × c × d² × √p, and the flow available at 20 psi residual is Q × ((static − 20) ÷ (static − residual))^0.54.
Key takeaways
- Two hydrants: a test (residual) hydrant with a gauge, and a flow hydrant downstream with a pitot gauge.
- Three readings: static pressure, residual pressure and pitot pressure.
- Q = 29.83 × c × d² × √p × number of outlets. c is 0.90 smooth, 0.80 sharp, 0.70 projecting.
- Project to 20 psi residual: Q20 = Q × ((S − 20) ÷ (S − R))^0.54.
- Aim for a static-to-residual drop of at least 10 psi. Open and close hydrants slowly to prevent water hammer.
What is a hydrant flow test?
A hydrant flow test (also called a fire flow test) shows how much water the distribution system can deliver at one location and how far pressure falls when it does. The result is the fire flow available at that location, expressed at 20 psi residual.
The test needs two hydrants. The test hydrant, also called the residual hydrant, is the one nearest the property, and it carries a pressure gauge. The flow hydrant is the next hydrant downstream, and it is the one you open. Pressures are read at the residual hydrant, not at the hydrant that is flowing.
You record three numbers: static pressure (no flow), residual pressure (at the test hydrant while the flow hydrant runs) and pitot pressure (the velocity pressure in the stream leaving the flow hydrant).
| Reading | Where | What it tells you |
|---|---|---|
| Static pressure (S) | Test hydrant, before flowing | Normal system pressure at that spot |
| Pitot pressure (p) | Stream from the flow hydrant outlet | How fast water leaves the outlet, which gives the flow |
| Residual pressure (R) | Test hydrant, while flowing | How much pressure the main keeps under that flow |
Hydrant flow test procedure, step by step
This sequence follows the Tennessee Municipal Technical Advisory Service (MTAS) fire flow test reference. Your utility's own procedure comes first. Get the water utility's permission before operating any hydrant or valve, and notify the utility and the fire department before the test.
- Pick the two hydrants: the test hydrant nearest the site and the flow hydrant next downstream. Check both for damage and report any problems.
- Take a 2½-inch cap off the test hydrant, attach the gauge, and open the hydrant slowly. Give the gauge a few minutes to settle, then record the static pressure.
- Remove a cap on the flow hydrant (usually a 2½-inch outlet). Note the outlet type (smooth, sharp or projecting) by feeling the inside edge. Make sure the stream will not damage property; use a diffuser and control traffic if needed.
- Open the flow hydrant fully and slowly. When the stream is steady, read the pitot gauge in the stream. At the same moment, the other crew records the residual pressure.
- Close the flow hydrant slowly. Re-read static pressure at the test hydrant. If it matches the first reading, close the test hydrant slowly.
- Estimate the water used and report it to the utility, because it is unmetered water.
What is the hydrant flow test formula?
The discharge formula, sometimes called the Freeman or Underwriters formula, turns the pitot reading into gallons per minute: Q = 29.83 × c × d² × √p × N. Q is flow in gpm, c is the coefficient of discharge, d is the outlet's inside diameter in inches, p is the pitot pressure in psi and N is the number of outlets flowing. Some references print the constant as 29.84; the answer changes by well under 1%.
The coefficient depends on how the outlet meets the hydrant barrel, because a rough edge squeezes the stream. You feel the inside of the nozzle to decide. If you read the pitot inside a diffuser, use the diffuser's own coefficient (often 1.0) instead of the table. For outlets of 4 inches or larger, MTAS also applies a velocity-pressure correction (0.97 at 2 psi down to 0.83 at 7 psi and over).
| Outlet type (under 4 in) | Coefficient c | Flow at 16 psi pitot, 2½ in outlet |
|---|---|---|
| Smooth and rounded | 0.90 | 29.83 × 0.90 × 6.25 × 4 = 671 gpm |
| Square and sharp | 0.80 | 29.83 × 0.80 × 6.25 × 4 = 597 gpm |
| Square, projecting into barrel | 0.70 | 29.83 × 0.70 × 6.25 × 4 = 522 gpm |
How do you calculate flow at 20 psi residual?
The flow you measured is only the flow at the residual pressure you happened to reach. What designers want is the flow the main can give while it still holds 20 psi, the required residual in the MTAS method. The projection is Q20 = Q × ((S − 20) ÷ (S − R))^0.54, with S and R in psi.
The 0.54 exponent comes from the Hazen-Williams relationship (1 ÷ 1.85 ≈ 0.54): head loss grows with flow to the 1.85 power, so flow grows with pressure drop to the 0.54 power. The method assumes the system behaves the same at both flows. As hydraulics author Tom Walski points out, it can mislead if a pump runs out or a pressure-reducing valve did not open during the test.
For a good projection, MTAS says the static pressure should drop at least 10 psi once the flow hydrant is fully open. If it drops only a few psi, open another outlet or another hydrant and test again. On a calculator, use the yˣ or ^ key for the 0.54 power.
Worked hydrant flow test examples
Example 1 (one outlet). Static 72 psi. One smooth 2½-inch outlet, pitot 16 psi, residual 52 psi. Flow: 29.83 × 0.90 × 2.5² × √16 = 29.83 × 0.90 × 6.25 × 4 = 671.2, so 671 gpm. Drop: 72 − 52 = 20 psi, more than 10. Projection: (72 − 20) ÷ (72 − 52) = 52 ÷ 20 = 2.6; 2.6^0.54 = 1.675; 671 × 1.675 = 1,124 gpm available at 20 psi.
Example 2 (two outlets). Static 60 psi. Two smooth 2½-inch outlets flowing, each at 16 psi pitot; residual 45 psi. Flow: 29.83 × 0.90 × 6.25 × 4 × 2 = 1,342 gpm. Projection: (60 − 20) ÷ (60 − 45) = 40 ÷ 15 = 2.667; 2.667^0.54 = 1.698; 1,342.35 × 1.6983 = 2,279.8, so 2,280 gpm at 20 psi.
Example 3 (outlet type matters). One 2½-inch outlet, square and sharp (c = 0.80), pitot 25 psi: 29.83 × 0.80 × 6.25 × 5 = 745.75, so 746 gpm. Using 0.90 by mistake would give 839 gpm, 12.5% too high.
Example 4 (pressure in feet). 20 psi residual equals 20 × 2.31 = 46.2 ft of head. So a 20 psi residual means the hydraulic grade at the hydrant stays 46.2 ft above it. Use 2.31 ft/psi whenever an answer needs head instead of pressure.
| Example | Q during test | S − 20 | S − R | Ratio^0.54 | Q at 20 psi |
|---|---|---|---|---|---|
| 1 | 671 gpm | 52 | 20 | 1.675 | 1,124 gpm |
| 2 | 1,342 gpm | 40 | 15 | 1.698 | 2,280 gpm |
Safety and common mistakes
- Opening or closing fast. Hydrants must be opened and closed slowly to prevent damage from water hammer.
- Skipping the second static reading. A higher reading after the test can mean a pump started, so repeat with the pump off; a much lower reading can mean a main break.
- Wrong c. Feel the outlet; a sharp edge gives about 11% less flow than a smooth one at the same pitot reading.
- Using the outlet's nominal size without checking. d is the inside diameter in inches, and it is squared, so small errors grow.
- Forgetting the water. Flooded lawns and blocked traffic are real hazards; secure caps, use a diffuser where needed and report the volume flowed.
Practice this now — free
Get fast at pressure and flow math
Practice pressure, head and flow problems with full worked answers, then try a timed test.
Take the free math practice test →Frequently asked questions
What is the formula for a hydrant flow test?
Flow in gpm is Q = 29.83 × c × d² × √p × N, where c is the outlet coefficient (0.90 smooth, 0.80 sharp, 0.70 projecting), d is the outlet diameter in inches, p is the pitot pressure in psi and N is the number of outlets flowing. Flow at 20 psi residual is Q × ((static − 20) ÷ (static − residual))^0.54.
Why is 20 psi used in hydrant flow tests?
The standard projection rates available fire flow at 20 psi residual; Tennessee MTAS explains that pulling a main below 20 psi can damage the system or create backflow conditions. The flow you measured is projected to 20 psi with the 0.54-power formula.
How much should pressure drop during a hydrant flow test?
Tennessee MTAS says static pressure should drop at least 10 psi once the flow hydrant is fully open, and it quotes NFPA 291 as asking for a drop of at least 25% or a flow equal to the total firefighting demand. If the drop is smaller, flow more outlets or hydrants.
What is the difference between static and residual pressure?
Static pressure is read at the test hydrant with no water flowing nearby. Residual pressure is read at the same gauge while the flow hydrant is fully open. The difference shows how much pressure the main loses at that flow.
Which hydrant gets the pitot gauge?
The flow hydrant, the one that is open and discharging. The pitot gauge reads the velocity pressure of the stream leaving the outlet. The test hydrant carries the pressure gauge for static and residual readings.
Is hydrant flow testing on the water distribution exam?
Hydrant operation, pressure and flow math are common distribution exam topics, but each exam differs. Check your state's or ABC's need-to-know criteria and practice the pressure and flow formulas on the formula sheet.
Sources
- Conducting a Fire Flow Test (MTAS, University of Tennessee) ↗
Procedure, Q formula, c values, large-outlet correction, 20 psi projection, 10 psi drop, water-hammer and reporting cautions
- Where did this equation for hydrant flow test results come from? (Tom Walski, Bentley) ↗
Origin and assumptions of the 0.54-power 20 psi projection; pressures read at the residual hydrant
- Water flow test (Wikipedia) ↗
Alternate constant 29.84 and c = 1.0 with a diffuser
Mainsora is independent exam preparation, not affiliated with ABC/WPI, AWWA, EPA or any state certification program. Requirements change — confirm with your state program. See our editorial policy.