How many feet of 6-inch pipe hold 1,000 gal of water? (Round to the nearest foot.)
About this practice test
20 exam-style questions for the Georgia water distribution operator exam (ABC (state-administered)), across every topic on the test. Pick an answer, check it, read why.
Original practice questions written for Mainsora — not real exam items.
See all 20 questions with answers and explanations
How many feet of 6-inch pipe hold 1,000 gal of water? (Round to the nearest foot.)
Answer: 681 ft
Why: Length = volume (ft³) ÷ cross-sectional area (ft²) ≈ 681 ft.
- 1,000 gal ÷ 7.48 = 133.7 ft³
- 133.7 ÷ (0.785 × 0.5²) = 133.7 ÷ 0.196 = 681 ft
Each foot of water depth adds how much pressure?
- 0.0361 psi
- 0.433 psi
- 2.31 psi
- 62.4 psi
Answer: 0.433 psi
Why: 0.433 psi per foot is the reciprocal of 2.31 ft per psi.
Water is moving through an 8-inch main at 3.0 ft/s. What is the flow in cubic feet per second?
- 0.26 cfs
- 1.05 cfs
- 1.57 cfs
- 4.19 cfs
Answer: 1.05 cfs
Why: Q = A × V with the area in square feet and velocity in ft/s gives cubic feet per second; the 8-in pipe has 0.349 ft² of area.
- Convert diameter: 8 in ÷ 12 = 0.667 ft.
- Area = 0.785 × 0.667² = 0.349 ft².
- Q = A × V = 0.349 ft² × 3.0 ft/s = 1.05 cfs.
A 0.50 MG tank is to be filled to 10 mg/L chlorine using 65% calcium hypochlorite. How many pounds of calcium hypochlorite are needed? (Assume no chlorine demand.)
Answer: 64.2 lb
Why: Pounds of chlorine = 0.50 MG x 8.34 x 10 mg/L = 41.7 lb; divide by 0.65 purity to get about 64.2 lb of product.
- lb Cl2 = 0.50 MG x 8.34 lb/gal x 10 mg/L = 41.7 lb
- lb HTH = 41.7 / 0.65 = 64.2 lb
A booster station pumps 450 gpm. The chlorine demand is 1.8 mg/L and the target residual is 0.6 mg/L. How many pounds of 65% calcium hypochlorite will be used during one 12-hour shift?
Answer: 9.98 lb
Why: Find dose, convert flow, compute pounds per day of chlorine, take half a day, then divide by the 0.65 available-chlorine fraction.
- Dose = 1.8 + 0.6 = 2.4 mg/L
- Flow = 450 x 1,440 / 1,000,000 = 0.648 MGD
- Chlorine = 0.648 x 2.4 x 8.34 = 12.97 lb/day; for 12 hours = 6.49 lb
- Product = 6.49 / 0.65 = 9.98 lb of 65% calcium hypochlorite
A 12-inch main is capped (dead end) and will be tested at 150 psi. What is the thrust on the cap?
- 113 lb
- 1,800 lb
- 16,956 lb
- 67,824 lb
Answer: 16,956 lb
Why: Thrust on a plug equals pressure times the cross-sectional area: 0.785 x 12^2 in^2 x 150 psi = 16,956 lb.
- Area = 0.785 x 12 x 12 = 113.04 in^2
- Thrust = 113.04 x 150 = 16,956 lb
When tapping a horizontal main for a new service, at what position is the corporation stop typically installed?
- 12 o'clock, on top of the main
- 6 o'clock, on the bottom of the main
- 3 o'clock or 9 o'clock
- 10 o'clock or 2 o'clock
Answer: 10 o'clock or 2 o'clock
Why: The PA DEP manual gives 10 or 2 o'clock as the typical tap positions: off the crown of the main and well above its bottom.
Which set of observations most suggests a backflow incident has occurred in one neighborhood?
- Odor complaints, pressure drop, residual loss
- Higher fire flow, rising tank levels, and stable residual
- Higher TTHM, warm water, and long water age
- Rising pH, falling turbidity, and higher pressure
Answer: Odor complaints, pressure drop, residual loss
Why: Customer complaints, pressure drops, short-term loss of residual and meters running backward are typical indicators.
A high-lift station has had two main breaks shortly after power failures tripped all pumps at once. Which measure most directly addresses the cause?
- Install surge tanks and surge relief valves
- Add a second check valve on each pump discharge
- Install a larger altitude valve at the tank
- Raise the pump discharge pressure setting
Answer: Install surge tanks and surge relief valves
Why: Pumps stopping suddenly cause surges that can burst or collapse pipe. Surge tanks, pressure and surge relief valves, and vacuum relief valves are the listed control measures.
- Sudden pump stoppage creates transients (water hammer).
- Surge control devices reduce those pressure spikes and vacuums.
The total dynamic head a distribution pump must overcome is best described as:
- Static lift minus friction and minor losses
- Static lift only, measured at zero flow
- Friction and minor losses only, at design flow
- Static lift plus friction and minor losses
Answer: Static lift plus friction and minor losses
Why: The pump must supply the elevation difference plus the energy lost to friction and fittings at the operating flow.
A system has an LRAA of 0.092 mg/L TTHM at one location. Which public notice tier applies?
- None until two locations exceed
- Tier 1, within 24 hours
- Tier 3, within one year
- Tier 2, within 30 days
Answer: Tier 2, within 30 days
Why: MCL violations that are not listed as Tier 1 (like TTHM) require Tier 2 notice within 30 days, repeated every three months while the violation lasts.
A 150-lb chlorine cylinder is leaking from its side wall. If it can be moved safely, how should it be positioned?
- Leak on the bottom, so it drains out
- Leak on top, so gas escapes, not liquid
- Submerged in water to absorb it
- Upside down, valve end at the floor
Answer: Leak on top, so gas escapes, not liquid
Why: Liquid chlorine expands about 460 times when it vaporizes, so turning the leak to the top limits the release to gas.
A contractor finishes a main replacement, and the new pipe ended up 4 ft off the alignment shown on the design plans. What should be used to update the GIS and system map?
- The original design drawings
- The contractor's bid tabulation
- The valve card of the nearest valve
- As-built (record) drawings
Answer: As-built (record) drawings
Why: As-built or record drawings show what was actually installed, which can differ from the design. Maps must reflect repairs and replacements.
A procedure calls for flushing three pipe volumes through 2,000 ft of 6-inch main at 400 gpm. How many minutes of flushing are required? (Round to one decimal.)
Answer: 22 min
Why: Three volumes ≈ 8,807 gal ÷ 400 gpm ≈ 22 minutes.
- One volume = 0.785 × 0.5² × 2,000 × 7.48 = 2,936 gal; × 3 = 8,807 gal
- 8,807 ÷ 400 gpm = 22.0 min
A tank water surface is at elevation 950 ft. A pressure gauge on the main below is at elevation 835 ft. With no flow, what should the gauge read?
- 411.4 psi
- 361.6 psi
- 265.7 psi
- 49.8 psi
Answer: 49.8 psi
Why: Static pressure depends on the vertical distance between water surface and gauge: 115 ft × 0.433 ≈ 49.8 psi.
- Head = 950 − 835 = 115 ft
- 115 × 0.433 = 49.8 psi
A 0.75-MG tank is at 40% full. The pump delivers 1,100 gpm while system demand on the tank averages 400 gpm. How many hours to reach 95% full?
- 4.58 hr
- 6.25 hr
- 9.82 hr
- 17.86 hr
Answer: 9.82 hr
Why: Only 55% of the tank must be filled, and only the net 700 gpm adds to storage, so about 9.8 hours.
- Volume needed = 750,000 × 0.55 = 412,500 gal.
- Net inflow = 1,100 − 400 = 700 gpm.
- 412,500 ÷ 700 = 589 min ÷ 60 = 9.82 hr.
During a main-break repair, what should be done to the inside of the repair sleeve, fittings and the new pipe section before installation?
- Rinse them with dechlorinated water
- Coat them with pipe joint lubricant only
- Swab them with 1% hypochlorite
- Wipe them with a dry, clean cloth
Answer: Swab them with 1% hypochlorite
Why: Repair pipe, fittings and valves are swabbed with a 1% hypochlorite solution to disinfect surfaces that will touch potable water.
A chlorinator is set at 18 lb/day and the plant flow is 1.1 MGD. What chlorine dose is being applied?
- 165 mg/L
- 16.4 mg/L
- 2.0 mg/L
- 0.51 mg/L
Answer: 2.0 mg/L
Why: Rearranging the pounds formula gives dose = 18 / (1.1 x 8.34) = 2.0 mg/L.
- Dose = lb/day / (MGD x 8.34)
- Dose = 18 / (1.1 x 8.34) = 18 / 9.17 = 2.0 mg/L
Before a length of pipe is lowered into the trench, what should the crew do?
- Fill it with water from the trench to check for leaks
- Remove the gasket from the bell to check its fit
- Inspect it for damage and clean the interior
- Coat the interior with grease to ease assembly
Answer: Inspect it for damage and clean the interior
Why: Pipe should be inspected for damage and contamination, cleaned, and sealed with watertight plugs when construction is halted.
An operator finds water discharging from an elevated tank overflow every night when demand is low, although SCADA shows the booster pumps are off. Which component should be checked first?
- The air release valve on the tank riser pipe
- The cathodic protection system
- The tank vent screen
- The altitude valve on the tank inlet
Answer: The altitude valve on the tank inlet
Why: Repeated overflow with gravity filling means the level control is not closing. The altitude valve is designed to close at the high level and prevent overflow.
- With pumps off, the tank is filling from system pressure.
- The valve that should stop filling at the high level is the altitude valve.
Georgia exam at a glance
- Exam
- ABC (state-administered)
- Questions
- 100
- Formula sheet
- WPI provides its Formula/Conversion Table during ABC standardized exams
Ready for the full exam experience?
The full course adds every lesson as a hands-on illustration, all practice questions with worked solutions and two timed 100-question practice exams. One-time payment from $29.
Common questions
How many questions are on the Georgia water distribution exam?
The Georgia distribution exam has 100 questions (ABC (state-administered)).
Is this practice test free?
Yes — 20 questions with instant explanations, no sign-up. Math questions show every step.
Can I use a formula sheet on the exam?
ABC/WPI exams come with a formula/conversion table, and many state-written exams provide one too; check your state's candidate information. Our explanations use the same standard constants (7.48 gal/ft³, 8.34 lb/gal, 2.31 ft/psi, 0.785 D²).
How should I use a practice test?
Answer before peeking, read every explanation (even when you're right), and go back to the lesson for any topic you miss. Take a full timed 100-question practice exam a week before test day.