Maryland Water Distribution Practice Test

20 free exam-style questions for the Maryland exam. Instant explanations, no sign-up.

Question 1 of 20Math: area, volume and conversions

What is the cross-sectional area of a 12-inch main, in square feet?

Pick an answer and check it.

About this practice test

20 exam-style questions for the Maryland water distribution operator exam (State Board (vendor not confirmed)), across every topic on the test. Pick an answer, check it, read why.

Original practice questions written for Mainsora — not real exam items.

See all 20 questions with answers and explanations
  1. What is the cross-sectional area of a 12-inch main, in square feet?

    • 0.196 ft²
    • 0.785 ft²
    • 1.570 ft²
    • 3.140 ft²

    Answer: 0.785 ft²

    Why: Area of a circle = 0.785 × D² with D in feet; a 1-ft diameter gives 0.785 ft².

    1. Convert diameter: 12 in ÷ 12 = 1 ft
    2. A = 0.785 × (1 ft)² = 0.785 ft²
  2. Each foot of water depth adds how much pressure?

    • 0.0361 psi
    • 0.433 psi
    • 2.31 psi
    • 62.4 psi

    Answer: 0.433 psi

    Why: 0.433 psi per foot is the reciprocal of 2.31 ft per psi.

  3. A new 12-inch main is to be flushed at 5 ft/s. What flow must be discharged?

    • 29 gpm
    • 236 gpm
    • 1,762 gpm
    • 7,046 gpm

    Answer: 1,762 gpm

    Why: A 12-in main has 0.785 ft² of area; at 5 ft/s that is 3.93 cfs, or about 1,762 gpm.

    1. A = 0.785 × (1 ft)² = 0.785 ft².
    2. Q = 0.785 × 5 = 3.925 cfs.
    3. 3.925 × 7.48 × 60 = 1,762 gpm.
  4. When a DPD test is run for total chlorine instead of free chlorine, the reagent includes an added chemical that lets chloramines react. What is it?

    • Sodium thiosulfate
    • Ammonium hydroxide
    • Sodium hydroxide
    • Potassium iodide

    Answer: Potassium iodide

    Why: Iodide is oxidized by chloramines to iodine, which then reacts with DPD, so the color shows free plus combined chlorine.

  5. A system treats 1.2 MGD at 2.0 mg/L with 12.5% sodium hypochlorite. Assuming the solution weighs 8.34 lb/gal, how many gallons of hypochlorite are fed per day?

    • 0.30 gal/day
    • 2.4 gal/day
    • 19.2 gal/day
    • 160 gal/day

    Answer: 19.2 gal/day

    Why: Each gallon of 12.5% solution carries about 1.04 lb of chlorine, so 20.0 lb/day needs 19.2 gal/day.

    1. Chlorine = 1.2 x 2.0 x 8.34 = 20.0 lb/day
    2. Available chlorine per gallon = 8.34 x 0.125 = 1.04 lb/gal
    3. Gallons = 20.0 / 1.04 = 19.2 gal/day
  6. A new water main must cross a sanitary sewer. Under Ten States Standards, what is the minimum vertical separation and preferred position?

    • 18 inches, water main above the sewer
    • 18 inches, water main below the sewer
    • 6 inches, water main above the sewer
    • 10 feet, water main above the sewer

    Answer: 18 inches, water main above the sewer

    Why: Crossings require at least 18 inches between the outside of the water main and outside of the sewer, with preference for the water main above.

  7. Which automatic meter reading approach collects readings by short-range radio as a reader drives past, without touching each meter?

    • Fixed-network data collection
    • Handheld touch-pad data collection
    • Manual visual reading
    • Mobile data collection

    Answer: Mobile data collection

    Why: Mobile data collection uploads readings by short-range radio to a logger in a passing vehicle. Fixed-network systems can report as often as every 15 minutes.

  8. A factory has an RP at its service connection. Inside, a process tank has a submerged hose. Who is protected by the RP?

    • The factory's users, but not the public system
    • Both the public system and every factory outlet
    • Neither, because the hose is inside the building
    • The public system only, not the factory's users

    Answer: The public system only, not the factory's users

    Why: Containment shields the public system from the premises but does not protect people inside; internal hazards need fixture protection by the owner.

  9. In an AWWA/IWA-style water audit, which of these is classified as an APPARENT loss?

    • Customer meter under-registration
    • Overflow from a storage tank
    • Leakage at a main joint
    • Leakage from a broken service line before the meter

    Answer: Customer meter under-registration

    Why: Apparent losses are unauthorized consumption, customer metering inaccuracies, and data handling errors. The water is used but not billed.

    1. Real losses = physical water escaping.
    2. Apparent losses = water used but not recorded or billed, such as meter inaccuracy, theft, and data errors.
  10. A pump delivers 1,500 gpm at 175 ft TDH. Pump efficiency is 80% and motor efficiency is 92%. It runs 20 hours a day and power costs $0.11 per kWh. What is the daily energy cost in dollars?

    Answer: 147.82 $

    Why: Find motor horsepower from flow, head and both efficiencies, convert to kW, multiply by hours and rate.

    1. mhp = 1,500 × 175 ÷ (3,960 × 0.80 × 0.92) = 90.1 hp.
    2. kW = 90.1 × 0.746 = 67.2 kW; kWh = 67.2 × 20 = 1,344 kWh.
    3. Cost = 1,343.8 kWh × $0.11 = $147.82.
  11. How long must records of chemical analyses be kept?

    • 3 years
    • 5 years
    • 10 years
    • 15 years

    Answer: 10 years

    Why: Under 40 CFR 141.33(a), records of chemical analyses must be kept at least 10 years (lead and copper program records under 141.91 must be kept 12 years).

  12. A crew is opening a trench in Type B soil to replace a section of main. Unless the cut is entirely in stable rock, at what depth does OSHA require a cave-in protective system no matter what the competent person thinks?

    • 4 ft
    • 5 ft
    • 6 ft
    • 20 ft

    Answer: 5 ft

    Why: 29 CFR 1926.652(a)(1) requires a protective system unless the excavation is in stable rock or is less than 5 ft deep and a competent person finds no cave-in potential. At 5 ft and deeper, protection is mandatory.

  13. A main break flowed an estimated 350 gpm for 2.5 hours before it was isolated. How many gallons were lost?

    • 875 gal
    • 21,000 gal
    • 52,500 gal
    • 1,260,000 gal

    Answer: 52,500 gal

    Why: 350 gpm × 2.5 h × 60 min/h = 52,500 gal.

    1. 2.5 h × 60 min/h = 150 min.
    2. 350 gpm × 150 min = 52,500 gal.
  14. A procedure calls for flushing three pipe volumes through 2,000 ft of 6-inch main at 400 gpm. How many minutes of flushing are required? (Round to one decimal.)

    Answer: 22 min

    Why: Three volumes ≈ 8,807 gal ÷ 400 gpm ≈ 22 minutes.

    1. One volume = 0.785 × 0.5² × 2,000 × 7.48 = 2,936 gal; × 3 = 8,807 gal
    2. 8,807 ÷ 400 gpm = 22.0 min
  15. What force, in pounds, acts on a dead-end cap of a 24-inch main at 80 psi? (Round to the nearest pound.)

    Answer: 36,173 lb

    Why: Force = psi × in²; a 24-inch cap at 80 psi sees about 36,000 lb.

    1. Area = 0.785 × 24² = 452.2 in²
    2. 452.2 × 80 = 36,173 lb
  16. A booster station is pumping 900 gpm. What is this flow in cfs?

    • 120.32 cfs
    • 15.00 cfs
    • 2.01 cfs
    • 1.30 cfs

    Answer: 2.01 cfs

    Why: Divide gpm by 7.48 to get ft³/min, then by 60 to get ft³/s: about 2.01 cfs.

    1. 900 gpm ÷ 7.48 = 120.3 ft³/min.
    2. 120.3 ÷ 60 = 2.01 cfs.
  17. Why do TTHM results at the same distribution sites usually peak in late summer?

    • Faster reactions and higher chlorine demand
    • Summer demand shortens water age throughout the system
    • Source water bromide is removed by summer algae growth
    • Chlorine is less reactive with organics in warm water

    Answer: Faster reactions and higher chlorine demand

    Why: Reactions go faster and further at higher temperature, and higher chlorine demand often means a higher dose, so DBP formation potential rises.

  18. A chlorinator is set at 18 lb/day and the plant flow is 1.1 MGD. What chlorine dose is being applied?

    • 165 mg/L
    • 16.4 mg/L
    • 2.0 mg/L
    • 0.51 mg/L

    Answer: 2.0 mg/L

    Why: Rearranging the pounds formula gives dose = 18 / (1.1 x 8.34) = 2.0 mg/L.

    1. Dose = lb/day / (MGD x 8.34)
    2. Dose = 18 / (1.1 x 8.34) = 18 / 9.17 = 2.0 mg/L
  19. At a water-sewer crossing, how should the water pipe be positioned?

    • Center one full pipe length over the sewer
    • Put a joint directly over the sewer for access
    • Place a joint on each side, close to the sewer
    • Encase a joint in concrete over the sewer

    Answer: Center one full pipe length over the sewer

    Why: One full length of water pipe is centered at the crossing so both joints are as far from the sewer as possible.

  20. According to the Pennsylvania DEP operator training manual, distribution system valves should be inspected and exercised at least:

    • Once every 5 years
    • Once every 3 years
    • Only after a main break
    • Once per year

    Answer: Once per year

    Why: Annual inspection and exercising keeps valves operable and confirms their locations match system maps.

Maryland exam at a glance

Exam
State Board (vendor not confirmed)
Passing score
69.5% (COMAR 26.06.01.10)

Read the full Maryland guide →

Ready for the full exam experience?

The full course adds every lesson as a hands-on illustration, all practice questions with worked solutions and two timed 100-question practice exams. One-time payment from $29.

Common questions

How many questions are on the Maryland water distribution exam?

Maryland does not publish the question count on an official page we could verify; check the current candidate handbook from Maryland State Board of Waterworks and Waste Systems Operators (Maryland Department of the Environment).

Is this practice test free?

Yes — 20 questions with instant explanations, no sign-up. Math questions show every step.

Can I use a formula sheet on the exam?

ABC/WPI exams come with a formula/conversion table, and many state-written exams provide one too; check your state's candidate information. Our explanations use the same standard constants (7.48 gal/ft³, 8.34 lb/gal, 2.31 ft/psi, 0.785 D²).

How should I use a practice test?

Answer before peeking, read every explanation (even when you're right), and go back to the lesson for any topic you miss. Take a full timed 100-question practice exam a week before test day.