Montana Water Distribution Practice Test

20 free exam-style questions for the Montana exam. Instant explanations, no sign-up.

Question 1 of 20Math: area, volume and conversions

Spoil from a trench 250 ft long, 3 ft wide and 5 ft deep will be hauled in trucks that carry 10 yd³ each. How many full or partial truckloads are needed? (Whole number.)

Pick an answer and check it.

About this practice test

20 exam-style questions for the Montana water distribution operator exam (ABC (state-administered)), across every topic on the test. Pick an answer, check it, read why.

Original practice questions written for Mainsora — not real exam items.

See all 20 questions with answers and explanations
  1. Spoil from a trench 250 ft long, 3 ft wide and 5 ft deep will be hauled in trucks that carry 10 yd³ each. How many full or partial truckloads are needed? (Whole number.)

    Answer: 14 loads

    Why: 138.9 yd³ needs 14 loads; a partial load still requires a trip. (Ignores soil swell.)

    1. V = 250 × 3 × 5 = 3,750 ft³ ÷ 27 = 138.9 yd³
    2. 138.9 ÷ 10 = 13.9 → 14 loads
  2. A hydrant at elevation 500 ft reads 90 psi static. What is the elevation of the hydraulic grade line at that point, in feet? (Round to one decimal.)

    Answer: 707.9 ft

    Why: HGL elevation = ground (gauge) elevation + pressure head in feet.

    1. 90 psi × 2.31 = 207.9 ft of pressure head
    2. 500 + 207.9 = 707.9 ft
  3. A 2.0-MG elevated tank averages 65% full. The volume that flows out (and is replaced) each day averages 0.40 MG. Estimate the average detention time (water age) in the tank.

    • 0.31 days
    • 3.25 days
    • 5.00 days
    • 7.69 days

    Answer: 3.25 days

    Why: Detention time is stored volume divided by the flow through it: 1.30 MG ÷ 0.40 MGD = 3.25 days.

    1. Average stored volume = 2.0 MG × 0.65 = 1.30 MG.
    2. Detention time = 1.30 MG ÷ 0.40 MG/day = 3.25 days.
  4. Routine samples show 0.6 mg/L free chlorine at nearby looped mains but only a trace at a hydrant on a long dead-end main serving three homes. What is the most appropriate first operational response?

    • Flush the dead end now and on a routine schedule
    • Raise the plant chlorine dose until the dead end reads 0.6 mg/L
    • Close the valve feeding the dead end until demand increases
    • Switch the sample site to a looped main with better residual

    Answer: Flush the dead end now and on a routine schedule

    Why: Stagnant water in dead ends loses residual; flushing replaces it with fresh water, and routine flushing (or looping) keeps water age down.

  5. A booster station pumps 450 gpm. The chlorine demand is 1.8 mg/L and the target residual is 0.6 mg/L. How many pounds of 65% calcium hypochlorite will be used during one 12-hour shift?

    Answer: 9.98 lb

    Why: Find dose, convert flow, compute pounds per day of chlorine, take half a day, then divide by the 0.65 available-chlorine fraction.

    1. Dose = 1.8 + 0.6 = 2.4 mg/L
    2. Flow = 450 x 1,440 / 1,000,000 = 0.648 MGD
    3. Chlorine = 0.648 x 2.4 x 8.34 = 12.97 lb/day; for 12 hours = 6.49 lb
    4. Product = 6.49 / 0.65 = 9.98 lb of 65% calcium hypochlorite
  6. Ten 1-lb tablets of 65% available chlorine are placed in a new 10-inch main 7,500 ft long. What chlorine dose results?

    • 16.6 mg/L
    • 25.5 mg/L
    • 39.2 mg/L
    • 190.6 mg/L

    Answer: 25.5 mg/L

    Why: Volume = 0.785 x (10/12)^2 x 7,500 x 7.48 = 30,594 gal = 0.0306 MG. Available chlorine = 10 x 0.65 = 6.5 lb. Dose = 6.5 / (8.34 x 0.0306) = 25.5 mg/L.

    1. Vol = 0.785 x 0.8333^2 x 7,500 x 7.48 = 30,594 gal = 0.030594 MG
    2. Dose = (10 x 0.65) / (8.34 x 0.030594) = 25.5 mg/L
  7. When setting a new traffic-model dry-barrel hydrant, about where should the break (breakaway) flange end up relative to finished grade?

    • Flush with the ground
    • About 12 inches above the ground
    • About 6 inches below the ground
    • About 2 inches above the ground

    Answer: About 2 inches above the ground

    Why: The break flange should be about 2 inches above the ground, so a vehicle strike breaks the hydrant at the flange rather than below grade.

  8. Per the installation figures in the EPA manual, an RP assembly installed horizontally indoors should be set at what height above the floor?

    • 12 inches minimum to 30 inches maximum
    • 6 inches minimum to 12 inches maximum
    • 36 inches minimum to 60 inches maximum
    • At floor level with a funnel drain

    Answer: 12 inches minimum to 30 inches maximum

    Why: The figures show RPs set 12 in minimum and 30 in maximum above the floor (and 12 in from walls) to keep the relief port above flooding and allow testing.

  9. On a centrifugal pump head-capacity curve, where is the highest head (shutoff head) found?

    • At maximum flow
    • At zero flow
    • Where the efficiency curve crosses the head curve
    • At the best efficiency point

    Answer: At zero flow

    Why: Head falls as flow rises along a centrifugal pump curve. The highest head is at zero flow, which is the shutoff head.

    1. As flow increases, the head a centrifugal pump can produce decreases.
    2. So the maximum head is at zero flow, the shutoff head.
  10. On a booster pump, suction pressure rises from 20 psi to 35 psi while discharge pressure stays at 90 psi. How does the total dynamic head on the pump change?

    • Increases by about 35 ft
    • Decreases by about 6 ft
    • Decreases by about 15 ft
    • Decreases by about 35 ft

    Answer: Decreases by about 35 ft

    Why: The pump only supplies the pressure difference; 15 psi more on the suction is about 35 ft less head.

    1. Old TDH = (90 − 20) × 2.31 = 161.7 ft; new = (90 − 35) × 2.31 = 127.1 ft.
    2. Change = 15 psi × 2.31 = 34.7 ft lower.
  11. How long must records of chemical analyses be kept?

    • 3 years
    • 5 years
    • 10 years
    • 15 years

    Answer: 10 years

    Why: Under 40 CFR 141.33(a), records of chemical analyses must be kept at least 10 years (lead and copper program records under 141.91 must be kept 12 years).

  12. Before entering a permit space, the atmosphere is tested with a multi-gas meter. In what order must the hazards be checked?

    • Flammables, oxygen, then toxics
    • Toxics, oxygen, then flammables
    • Oxygen, toxics, then flammables
    • Oxygen, flammables, then toxics

    Answer: Oxygen, flammables, then toxics

    Why: 1910.146(c)(5)(ii)(C) and (d)(5)(iii) require testing for oxygen first, then flammable gases and vapors, then toxic contaminants.

  13. Which item must an AWIA risk and resilience assessment evaluate?

    • Content of the annual CCR
    • The lead service line inventory
    • The coliform sample siting plan
    • Automated systems and their security

    Answer: Automated systems and their security

    Why: The RRA must assess the resilience of electronic, computer, and other automated systems, including their security, along with physical assets, monitoring, financial infrastructure, chemicals, and O&M.

  14. A small clearwell holds 2,500 ft³ of water. How many gallons is that?

    Answer: 18,700 gal

    Why: Multiply cubic feet by 7.48 to get gallons.

  15. A pressure zone has a hydraulic grade line at 1,020 ft. What is the static pressure at a house at elevation 850 ft?

    • 441.7 psi
    • 392.7 psi
    • 368.1 psi
    • 73.6 psi

    Answer: 73.6 psi

    Why: Pressure = (HGL − elevation) × 0.433 = 73.6 psi.

    1. Head = 1,020 − 850 = 170 ft
    2. 170 × 0.433 = 73.6 psi
  16. A community of 9,500 people uses an average of 140 gpcd. If the maximum-day factor is 1.8, what is the maximum-day demand in MGD?

    Answer: 2.39 MGD

    Why: Average demand times the max-day factor gives about 2.39 MGD.

    1. Average day = 140 × 9,500 = 1,330,000 gpd.
    2. Max day = 1,330,000 × 1.8 = 2,394,000 gpd = 2.39 MGD.
  17. A 0.50 MG tank is to be filled to 10 mg/L chlorine using 65% calcium hypochlorite. How many pounds of calcium hypochlorite are needed? (Assume no chlorine demand.)

    Answer: 64.2 lb

    Why: Pounds of chlorine = 0.50 MG x 8.34 x 10 mg/L = 41.7 lb; divide by 0.65 purity to get about 64.2 lb of product.

    1. lb Cl2 = 0.50 MG x 8.34 lb/gal x 10 mg/L = 41.7 lb
    2. lb HTH = 41.7 / 0.65 = 64.2 lb
  18. A crew placed 2.0 lb of 65% calcium hypochlorite in 600 ft of 8-inch main before filling it. What chlorine concentration will result once the main is full (ignore demand)?

    • 66 mg/L
    • 99 mg/L
    • 153 mg/L
    • 830 mg/L

    Answer: 99 mg/L

    Why: Only 1.3 lb of the product is chlorine; spread through 1,567 gal it gives about 99 mg/L, far above the 25 mg/L target.

    1. Volume = 0.785 x 0.667^2 x 600 x 7.48 = 1,567 gal = 0.001567 MG
    2. Chlorine = 2.0 x 0.65 = 1.3 lb
    3. mg/L = 1.3 / (0.001567 x 8.34) = 99 mg/L
  19. At a water-sewer crossing, how should the water pipe be positioned?

    • Center one full pipe length over the sewer
    • Put a joint directly over the sewer for access
    • Place a joint on each side, close to the sewer
    • Encase a joint in concrete over the sewer

    Answer: Center one full pipe length over the sewer

    Why: One full length of water pipe is centered at the crossing so both joints are as far from the sewer as possible.

  20. A flow test shows a hydrant can deliver 780 gpm at 20 psi residual. Using the NFPA color code, the top and caps should be painted:

    • Orange
    • Blue
    • Green
    • Red

    Answer: Orange

    Why: 780 gpm is in the 500–999 gpm range, which is orange (marginally adequate flow).

    1. 780 gpm falls in the 500–999 gpm class.
    2. That class is orange.

Montana exam at a glance

Exam
ABC (state-administered)
Formula sheet
DEQ posts a Drinking Water Formula/Conversion Table; WPI (formerly ABC) states its standardized exams are given with a formula/conversion table.

Read the full Montana guide →

Ready for the full exam experience?

The full course adds every lesson as a hands-on illustration, all practice questions with worked solutions and two timed 100-question practice exams. One-time payment from $29.

Common questions

How many questions are on the Montana water distribution exam?

Montana does not publish the question count on an official page we could verify; check the current candidate handbook from Montana Department of Environmental Quality, Water and Wastewater Operator Certification Program.

Is this practice test free?

Yes — 20 questions with instant explanations, no sign-up. Math questions show every step.

Can I use a formula sheet on the exam?

ABC/WPI exams come with a formula/conversion table, and many state-written exams provide one too; check your state's candidate information. Our explanations use the same standard constants (7.48 gal/ft³, 8.34 lb/gal, 2.31 ft/psi, 0.785 D²).

How should I use a practice test?

Answer before peeking, read every explanation (even when you're right), and go back to the lesson for any topic you miss. Take a full timed 100-question practice exam a week before test day.